• 검색 결과가 없습니다.

ects of Pres Sim

N/A
N/A
Protected

Academic year: 2022

Share "ects of Pres Sim"

Copied!
2
0
0

로드 중.... (전체 텍스트 보기)

전체 글

(1)

Experi

In LOCA of EQ(Equ specified b NPPs(Nucle LOCA envi shorten this usually app IEEE Std.

degradation and aging t equivalent t Although s activation en effects are i most reason [2].

Although profile(one days), it ma pressure co equipment.

plays an imp the effects performance condition.

In this pa equipment different p switches.

Test spec and LS-T. T to another p 1. In perfo criteria of th Table 1 O Contact

point C N 1-2 3-4 5-6 7-8

O

mental Stu

1.

A(Loss Of Coo uipment Qu by accident ear Power P ironment is on s long test p ply aging ass

1205-2000 [ n of equipmen time and tem time and temp some limitat nergy of spec ncluded, the m nable solution h this metho

year) into s ay be justified ondition has n In case of e portant role in of pressure e will be as aper, we exam integrity dur pressure prof

2.

cimens are tw The limit swi point by movi ormance test, he limit switch

Operation prin Connecting stat

ormal Lever

O X X O X O O X O: connecting,

udy for Effe

Byu K

Introduction olant Acciden ualification),

environmenta Plants). Gene ne year in do profile, most sessment meth 1]. This met nt is a functio mperature can

perature by Ar tions such a cimen and disr method is gen for shortenin od convenien shortened pro d under the as no effects on equipment wh n its performa

condition on significant as mine the press

ring LOCA t files to two

Experiment wo limit switc itch transfers ing lever as p one exampl h is as follows nciple of limit tus

r on S

<norma , X: disconne

ects of Pres Sim

ung-ju Lim, C Korea Institute

bzo

n

nt) simulation test profile al conditions eral duration omestic NPPs test laborato hod presented thod defines on of temperat be changed rrhenius equat as constancy regard of pres nerally used as ng long test pe tly modify ofile(less than ssumption that n performance hich sealing ance maintena n the equipm s the tempera

ure effects on test by apply o identical l

ches named L electrical cur presented in T le of accepta s.

t switch

Schematic

al> <Lever o ecting

ssure Cond mulation T

Chang-dae Par e of Machinery [email protected]

n test e is

s of n of . To ories d in

that ture, into tion.

y of ssure

s the eriod long n 30

t the e of

part ance, ment ature n the ying limit

LS-R rrent Table ance

x x

x

E Fig prep day The test perf iden 2.1

R agin LO sho pre and the pro case exp 2.2

faci boil che sev

n>

dition on Eq Test

rk, Chi-sung S y and Materia re.kr

Insulation res ground: over Dielectric str ground: endu minute Electric con resistance les EQ test proce . 1. Prior to th pared in exac y, chamber, an e functional te t, and LOCA

formed in tw ntical tempera

LOCA Test co Required test ng assessmen

CA profiles o own in Fig. 3

ssure is accel d 252.0 kPa, re specimen LS file in Fig. 2 a e of temper posed to the sa Test Facilitie Figure 4 sh ility. It mainl ler, accumulat emical solution

eral control va

Fig. 1 EQ

quipment I

Song als

sistance betwe 10 MΩ apply rength betwee urance in app ntinuity of

s than 1 Ω dure for a lim he LOCA test ctly same agin nd tester until est is followed

A simulation wo different ature and chem

ondition profiles are nt method, w of one year to . The test pr lerated from espectively. In S-R is expose and LS-T to th rature profile ame test profil

s

hows schema ly consists of tor and superh n such as mix alves, and dat

Q test procedu

Integrity in

een each conta ying 500 Vdc en each conta lying 2,500 V

contact poin

mit switch is t, two limit sw ng conditions seismic quali d by seismic n tests are

pressure pro mical spray co

presented in we shortened o test profile ofile for temp 1001 second n case of press ed to the requ he test profile es, both spe le in Fig. 3.

atic diagram f steam gener

heater, sprayin xing tank and

ta acquisition

ure of limit sw

n LOCA

act point and act point and Vac during 1 nts: contact

presented in witches were such as test ification test.

qualification respectively ofiles under onditions.

n Fig. 2. By the required of 7 days as perature and at 128.0 oC sure profiles, uired LOCA e in Fig. 3. In

ecimens are

of the test rator such as

ng system of spray pump, system such

witch

Transactions of the Korean Nuclear Society Spring Meeting Gyeongju, Korea, May 29-30, 2008

615

(2)

100 101 102 103 104 105 106 107 125

150 175 200 225 250 275

300 Temperature

Pressure

Time [ Second ] Temperature [o F ]

0 10 20 30 40 50 60 70 80

start under 6.9 kPa and 48.9 oC

30 days 74.4 oC 121.1 oC

149.4 oC

365 days 64.1 kPa 227.5 kPa

Pressure [ psig ]

326.1 kPa

Fig. 2 Required LOCA profile

100 101 102 103 104 105 106

100 120 140 160 180 200 220 240 260 280 300 320 340

Temperature Pressure

Time [ Second ] Temperature [oF ]

Accelerating start, 1001 s

0 10 20 30 40 50 60 70 80

252.0 kPa 326.1 kPa

128.0 oC

Pressure [ psig ]

149.4 oC

Fig. 3 Test profile

Fig. 4 Schematics of LOCA test facility as PLC and LabVIEW software.

3. Results

The functional test is performed for two limit switches aged in different LOCA pressure condition.

The test results of the functional test before, during, and after the LOCA test are presented in Table 2.

Considering the acceptance criteria stated previously, the specimen LS-R maintained its integrity in performance and had no damages except for thermally aged stain. On the other hand, the specimen LS-T tested

in higher pressure condition did not need the requirement of acceptance criteria. For electric continuity test, contact resistances of contact points displayed in Table 1 have to maintain less than 1 ohm.

However, the resistances of the contact points were not satisfied with this criterion in functional test after the LOCA test. When disassembling the specimens, contact points of the specimen LS-T was intensely contaminated by steam and chemicals due to leakage of seal of limit switch case.

4. Conclusion

In LOCA simulation test of EQ, most test laboratories usually shorten test profile using aging assessment method which considers degradation related to temperature effect and regards that pressure condition has no effects on performance of a specimen. However, our test results in Table 2 show that higher test pressure may cause the critical failures in equipment performance after the LOCA simulation test. Therefore, pressure as well as temperature condition in LOCA simulation test should be considered as important factor in case of pressure-vulnerable equipment which sealing status has a critical effect on performance.

Table 2. Results of performance test for limit switches Performance Before test During test After test Insulation

resistance

LS-R 29.9 GΩ - 34.9 MΩ

LS-T 29.9 GΩ - -

Dielectric strength

LS-R Pass

LS-T Pass - -

Electric continuity,

[mΩ]

LS-R 60.9 57.8 64.2

LS-T Pass Pass Fail

REFERENCES

[1] IEEE Std 1205, “Assessing monitoring, and mitigating aging effects on Class 1E equipment used in nuclear power generating stations” (2000).

[2] C.D Park, B.J Lim, C.S Song, “Methodology for modification of LOCA environmental test profile”, NTHAS5, (2006).

Transactions of the Korean Nuclear Society Spring Meeting Gyeongju, Korea, May 29-30, 2008

616

참조

관련 문서

[r]

Tamara Kasavina Leonide Massine Anton Dolin Serge Lifar Frederick Frankin.. Vaslav Nijinsky Bronislava Nijinska Ninette de Valois Marie Rambert

• 의사결정에 필요한 관련원가를 찾아라...

수평각측정시 에 필요한 조정 전부, 횡선의 조정, 망원경수준기의 조정, 연직분도원

• 이바노프: 백조와 왕자의 2인무는 프티파가 확립한 그랑 파드되 형식에서 벗어나 단 하나의 확장된

그 말은 이제 화자의 뜻을 따라 움직여나갈 것이라 믿어지고 있는 것이다.. 그 말은

더욱 괴상히 여겨 이 튿날 사람을 보내어 거사의 안부를 물으니, 지방 사람이 가로되 거사가 죽은지 며칠 되었다 하였다. 사 자가 돌아와 거사의 죽음을 고하매 날짜를 따져보니

용이 말하되 비유컨대 한 손으로 치면 소리가 없고 두 손으로 치면 소리가 나는 것과 같으니 대란 물건은 합한 후 에야 소리가 나는 법이라 聖王이 소리로써 天下를 다스릴 瑞徵이니