• 검색 결과가 없습니다.

Controllers Design and Stability Analysis

문서에서 저작자표시 (페이지 88-112)

4. Power Quality Improvement in Grid-connected Hybrid AC-DC Microgrids

4.4. Controllers Design and Stability Analysis

81

82

4.4.1. Inner Current Control Loop – PI Controller

The PI controller GPI_i

 

s with gains KP i_ and KI_i in (4.29) is used to regulate the IC current to fundamental componentsI*IC d, and IIC q*, . The Ziegler–Nichols tuning method [66] was applied to design KP i_ and KI i_ . The integral gain is fixed, while the proportional gain is gradually increased to the critical gain that makes the tracking error

*

, , ,

IC d IC d IC d

errii unstable.

Fig. 4.6 shows the tracking error with different KP i_ , and the critical proportional gain is about 30.0. Thus, we chose controller gains KP i_ 5.0 and KI i_ 50.0 for good tracking performance and sufficient stability margin.

4.4.2. Inner Current Control Loop – RC

To track the 6nth

n1,2,

harmonic currents iIC d*, and iIC q*, , RC with the digitized transfer function in (4.39) is used:

   

 

_ _

_ 1

d

d T l i r i

RC i T

K Q z z

G z

Q z z

 

 (4.39)

In (4.39), the RC is composed of three parameters: the LPF Q z

 

, the phase lead term

Fig. 4.6 Tracking error errIC d, with different KP i_ .

83

_

zl i, and the controller gain Kr i_ . The LPF Q z

 

in (4.40) is used to provide a crossover frequency of about 2kHz without phase lag [57].

 

0.2 0.8 0.2 1

Q zz  z (4.40)

To compensate the phase lag caused by the IC output filter

Z

IC, the phase lead term

_

zl i is added to the RC transfer function, and l i_ is determined by reducing the phase

lag of z Gl i_ P

 

z in the high frequency range [57]. From Fig. 4.7, l i_ 3 is selected because it results in a phase lag of 2 for z Gl i_ P

 

z at 800Hz.

The controller gain Kr i_ is related to the RC performance and stability. High Kr i_

Fig. 4.8 Pole-zero map of 1Go i_  z with different Kr i_ . Fig. 4.7 Phase diagram of z Gl i_ P z with different l i_ .

84

results in good harmonic regulation but small stability margin, and vice versa. To design

_

Kr i, the stability of the inner current control loop was investigated. In (4.34) and (4.35), the closed-loop transfer function Gc i_

 

s is stable if and only if its denominator

_

 

1Go i s introduces all zeros inside the stable region. On the z-plane, the stable region is inside the unit circle [67], and we provide the pole-zero map of 1Go i_

 

z with different Kr i_ in Fig. 4.8. The figure shows that Kr i_ 4.0 makes the controller unstable because the zeros of 1Go i_

 

z are outside of the unit circle. Hence, Kr i_ 1.0 is chosen for adequate stability margin.

4.4.3. Inner Current Control Loop – R Controller

While RC deals with the 6nth

n1,2,

harmonics, the resonant controller R regulates the IC current to the references IIC d*, , and IIC q*, ,, which oscillate with frequency

2 f

AC. KR i_ is investigated to design the resonant controller’s transfer function in (4.30).

From the Bode diagram of Go i_

 

z in Fig. 4.9, a magnitude of 20dB for Go i_

 

z is sufficient to deal with second-order harmonics, so we choose KR i_ 5.0.

Fig. 4.9 Bode diagram of Go i_  z with different KR i_ .

85

4.4.4. Outer Voltage Control Loop –PI Controller

The outer voltage controller maintains

v

DC , VAC d, , , VAC d, , , andVAC q, , as their references by means of the PI controller GPI v_

 

s . Similar to the inner control loop,

_

 

GPI v s was designed using the Ziegler–Nichols tuning method, and the controller gains were selected as KP v_ 0.2 and KI v_ 2.0.

4.4.5. Outer Voltage Control Loop – RC

To regulate the harmonics vAC d, and vAC q, in the AC bus voltage to zero, the IC provides the harmonic currentsiIC d*, and iIC q*, to the AC bus with the aid of RC GRC v_

 

s in (22).

_

 

GRC v s is discretized as GRC v_

 

z by using a bilinear transform:

   

 

_v _v

_v 1

N l r

RC N

K Q z z

G z

Q z z

 

 (4.41)

To designGRC v_

 

z , we have to determine the LPF Q z

 

, the phase lead term zl v_ , and the gain Kr v_ . Similar to the inner current controller, Q z

 

in (4.40) is used. Because

_

zl v does not deal with any phase delay except the internal computing phase lag, the phase lead term is chosen as zl v_z1.

86

The system stability was analyzed to design the controller gain Kr v_ . Fig. 4.10 shows the pole-zero map of 1Go v_

 

z with various Kr v_ . The outer control loop is stable if and only if all the zeros of 1Go v_

 

z are located inside the unit circle [67], which is the stability margin on the z-plane. As shown in Fig. 4.10, Kr v_ 0.05 makes the IC controller unstable because at least one zero of 1Go v_

 

z is outside of the unit circle. Therefore, we chose Kr v_ 0.01 for proper harmonic current generation and a safe stability margin.

Fig. 4.10 Pole-zero map of 1Go v_  z with different Kr v_ .

87

4.5. Simulation Results

To validate the proposed IC controller, simulation results were obtained using PSIM software with the system parameters in TABLE 4.1. The proposed control algorithm was simulated under many different conditions, and the simulation cases are defined in TABLE 4.2.

TABLE 4.1 System Parameters.

Parameter Value Parameter Value

*

VDC 140 V  VAC d* , , 35 2 V 

RG 0.1  RIC 0.1 

LG 1.2 mH  LIC 1.2 mH 

RAC 10 

TABLE 4.2 Test Cases.

Case Grid voltage condition Nonlinear load

1 Balanced and sag No

2 Balanced and swell No

3 2 phase sag, 1 phase swell No

4 1 phase sag, 1 phase swell No

5 2 phase sag, 1 phase swell Yes

6 1 phase sag, 1 phase swell Yes

88

Fig. 4.11 Simulation results of case 1: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation.

Fig. 4.12 Simulation results of case 2: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation.

89

Fig. 4.13 Simulation results of case 3: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation.

Fig. 4.14 Simulation results of case 4: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation.

90

4.5.1. Cases 1-4

In cases 1-4, only grid voltage

v

G is abnormal, and there is no nonlinear load in HMGs.

Fig. 4.11 shows the simulated results for case 1, where the balanced grid voltage

v

G

sags 20% in normal conditions. Even though the AC bus voltage

v

AC seriously sags before compensation, it is enhanced to the desired magnitude of 50Vafter

T

s. As described in (4.7), a capacitive current is required to reinforce the sag voltage.

In Fig. 4.12, case 2 is investigated with 20% grid voltage swell. The swelled voltage becomes the nominal voltage, 50V, after compensation. To reduce the AC bus voltage magnitude, the IC acts as an inductor from the perspective of the AC MG, as in (4.6).

Fig. 4.13 shows the simulation results for case 3, where

v

G is unbalanced with 2 cases of phase sag and 1 phase swell. As shown in Fig. 4.13(b), the AC bus voltage is initially abnormal, and both phase B and C voltages sag. However, it becomes normal with the nominal AC voltage after compensation at

T

s as shown in Fig. 4.13(c).

In case 4, the grid voltage condition is 1 phase sag and 1 phase swell, and the simulation results are shown in Fig. 4.14. In Fig. 4.14(b), vAC b, sags, vAC a, swells, and there is a negative sequence in

v

ACbefore compensation. The IC with the proposed controller can simultaneously mitigate both sag/swell and imbalance after compensation in Fig. 4.14(c).

To remove the negative sequence voltage, IC injects negative sequence currentsIIC d*, , and

* , ,

IIC q into the AC bus, which are given in (4.16). To improve the sag or swell voltage, the IC provides positive-sequence reactive current IIC q*, , in (4.10).

91

Fig. 4.15 Simulation results of case 5: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation, (d) IC current.

92

Fig. 4.16 Simulation results of case 6: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation, (d) IC current.

93

4.5.2. Cases 5-6

In cases 5 and 6, a nonlinear load is utilized in HMGs with the same grid voltage conditions as those in cases 3 and 4, respectively. The simulation results for case 5 are shown in Fig. 4.15. Before power quality compensation, in Fig. 4.15(b), the quality

v

AC

is seriously degraded because of the abnormal grid voltage

v

G and nonlinear load.

THD of

v

AC is very high, and THD of each phase voltage is given in TABLE 4.3. After compensation, as shown in Fig. 4.15(c), the AC bus voltage is balanced with a nominal amplitude value of 50V, and THD of the phase voltage becomes very low. TABLE 4.3 shows the THDs, which are lower than 5% to comply with the IEEE 519-1992 standard [68]. To obtain good

v

AC regardless of severe grid and load conditions, the IC with the proposed controller supplies unbalanced and distorted current, as shown in Fig. 4.15(d).

Fig. 2.2 shows the results of case 6, where the grid voltage conditions are the same as that of case 4 except the nonlinear load. In Fig. 2.2(b), before compensation,

v

AC is unbalanced and highly distorted. However, after compensation, the voltage quality of

v

AC

is significantly improved with very low THDs in Fig. 2.2(c). Fig. 2.2(d) shows the IC compensating current to enhance power quality.

TABLE 4.3 THD Values of Simulation Results.

Case 5

THD (%) vAC a, vAC b, vAC c,

Before compensation 7.70 10.78 11.01

After compensation 2.35 2.35 2.36

Case 6

Before compensation 8.23 11.42 9.90

After compensation 2.32 2.33 2.33

94

4.5.3. DC Bus Voltage Restoration

To maintain the nominal DC bus voltage in spite of load variation, the IC controls fundamental active power

P

IC between the AC and DC MGs by means of the fundamental active current IIC d*, , in (4.8). Fig. 4.17 shows the performance of DC bus voltage restoration. The DC bus voltage is maintained with value of 140V

T

s.

Fig. 4.17 Simulation results of vDC restoration.

95

4.6. Experimental Results

The performance of the proposed IC control strategy was verified with the same parameters used in the simulation. A TMS320F28335 microcontroller was used to implement the IC controller. The system prototype is shown in Fig. 4.18.

Fig. 4.18 System prototype: (a) Grid simulator, (b) Scope and power quality analyzer, (c) Source for power converters, (d) Power circuit, (e) DSP boards, (f) Linear loads, (g) Nonlinear load.

96

Fig. 4.19 Experimental results of case 1: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation.

Fig. 4.20 Experimental results of case 2: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation.

97

Fig. 4.21 Experimental results of case 3: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation.

Fig. 4.22 Experimental results of case 4: (a) vAC waveform, (b) Magnified S1 before compensation, (c) Magnified S2 after compensation.

98

4.6.1. Cases 1-4

Fig. 4.19 shows the AC bus voltage

v

AC in case 1, where

v

G is balanced and there is 20% sag. In Fig. 4.19(b), although

v

AC is balanced, it sags before

T

s. After

T

s, the IC provides the AC bus capacitive current to reinforce the AC bus voltage, which is recovered to the desired magnitude, as shown in Fig. 4.19(c).

In case 2, even though

v

G has 20% swell,

v

AC approximately swell 10% before compensation because of the voltage drop on grid side impedance

Z

G, as shown in Fig.

4.20. To reduce

v

AC, the IC absorbs reactive power by generating an inductive current, and

v

AC recovers its nominal value.

In case 3, phase A of

v

G swells 20%, while phases B and C sag 20%. In Fig. 4.21(b),

v

AC becomes worse because of the abnormal grid voltage, and both vAC b, and vAC c, sag with peak voltages of40.48V and 41.29V . When IC starts compensation at

T

s, both

,

vAC b and vAC c, are reinforced to the nominal voltage of50V, as shown in Fig. 4.21(c).

In case 4, phase B of the grid voltage sags, and phase A swells. The AC bus voltage before compensation is shown Fig. 4.22(b). When the IC starts compensation at

T

s, the AC bus voltage becomes normal, as shown in Fig. 4.22(c).

99

Fig. 4.23 Experimental results of case 5: (a) vAC waveform, (b) Magnified S1 and power analysis before compensation, (c) Magnified S2 and power quality after compensation.

100

Fig. 4.24 Experimental results of case 6: (a) vAC waveform, (b) Magnified S1 and power analysis before compensation, (c) Magnified S2 and power quality after compensation.

101

4.6.2. Cases 5-6

In cases 5 and 6, a three-phase diode bridge is used as a nonlinear load in order to inject the

6n1

 

th n1, 2,

harmonic current into the AC bus. Before compensation,

v

AC

severely sags in phases B and C, which have root mean squared (RMS) fundamental voltage values of 27.416V and 27.742V , respectively, as shown in Fig. 4.23(b).

Moreover, the nonlinear load results in a very distorted

v

AC waveform with THD of 7.307%, 10.94%, and 11.31% for phases A, B, and C, respectively. Fig. 4.23(c) shows the AC bus voltage with a detailed THD analysis after compensation. The RMS value of the fundamental voltages of both vAC b, and vAC c, are 36.828V and 36.053V , respectively, which are close to the RMS reference voltage of 35V. On the other hand, to cancel out the effect of harmonics in

v

AC, the harmonic currents in (4.20) and (4.21) should be injected into the HMGs. Thus, THDs are lower than 2.600%.

The grid voltage conditions in case 6 are the same as in case 4. Fig. 4.24 shows the AC bus voltage together with the power quality in case 6. In Fig. 4.24(b),

v

AC is unbalanced with severe sag in phases B and C. It is also highly distorted, and the 5th harmonic component is dominant. In order to effectively mitigate the harmonics and imbalance, the IC starts the proposed control strategy at

T

s, and the AC bus voltage becomes normal.

102

4.6.3. DC Bus Voltage Restoration

In the DC MG, the DC bus voltage

v

DC is higher than its nominal voltage of 140V due to the low load demand before compensation, as shown in Fig. 4.25. After

T

s, the DC bus voltage is reduced within 400msbecause the IC controls the power from the DC to the AC MGs. Moreover, in the case of very high load demand by

R

DC, the DC bus voltage variation is mitigated because the IC transfers active power from the AC to the DC MGs by means of negative current I*IC d, , based on (4.8).

Fig. 4.25 Experimental results of vDC restoration.

103

4.7. Conclusion

In this chapter, we enabled an IC to simultaneously mitigate many power quality issues in grid-connected HMGs, such as sag, swell, unbalanced and distorted voltage in an AC MG, and variation of the DC MG voltage. With the proposed control strategy, the IC can provide the desired power between AC and DC MGs along with the current to enhance the HMGs power quality. The proposed IC control algorithm was realized without a central controller or communication link by measuring only the AC and DC bus voltage instead of detecting the load current and grid voltage. Therefore, power quality improvement in the HMGs is achieved conveniently and easily with low system cost.

Moreover, there is no circulating current problem since the existing IC replaces additional shunt or series power converters that are used to enhance power quality. We also provided the detailed controller design procedure by analyzing the system stability.

The performance of the proposed control strategy was proven by both a simulation and experiment with different severe grid and load conditions.

104

5. Frequency-Adaptive DC Ripple Voltage Mitigation in Grid-connected Hybrid AC-DC Microgrids

In hybrid AC-DC microgrids (HMGs), the utilized single-phase inverter (SPI) causes ripple voltage on DC bus, which means the degraded HMGs power quality. Moreover, in case of single-phase inverter with variable frequencies (SPI-VF), ripple voltage appears at different frequencies. To adaptively mitigate the ripple voltage at different frequencies in grid-connected HMGs, this chapter proposes a frequency-adaptive control strategy for the existing interlinking converter (IC) which is used to link AC and DC microgrids (MGs).

By exploiting the existing IC, system cost as well as complexity are reduced significantly because additional ripple eliminators (REs) in DC MG are not mandatory. To deal with ripple voltage issue, IC injects ripple current to DC MG. In the proposed IC control scheme, IC ripple current reference is generated by measuring only the DC bus voltage. In other words, SPI current is not required in the proposed IC controller. Therefore, we needed not implement communication links between IC and SPI although SPIs are widely distributed in MG. Additionally, the proposed IC control technique also offers DC bus voltage restoration despite of wide variation of load power. As a result, DC bus voltage is ripple-free at the nominal voltage. Simulation and experimental results are provided to validate the performance.

105

문서에서 저작자표시 (페이지 88-112)

관련 문서