Choosing a Better Steam Trap

Seven years of extensive testing leads to an improved Engineering Design Guide

Seven years of performance monitoring and testing of steam traps at ICI’s Huddersfield and Grangemouth Works (England), along with performance and live steam loss tests at two manufacturers’ laboratories, culminated in a revised ICI Engineering Design Guide for the selection of steam traps, EDG. PIP. 30.01 A.

The old selection standards had a number of shortcomings, the most notable being that there was no reference to the type of equipment being drained nor to the method of drainage. Traps were often being selected for duties to which they were not suited.

In particular the

thermodynamic disc trap (around which the standards were largely based) has come to be regarded as a ‘trap for all seasons’, especially at the plant level.

Monitoring of trap performance began at Grangemouth Works in 1980 and two years later at Huddersfield Works, following complaints from engineering maintenance fitters of poor

service life on steam distribution mains drains.

Trap surveys were carried out to establish the types in use and to check the original selection for the duty. Testing programs were also implemented. Initial results were quite startling.

One plant survey of 415 traps showed 19% had failed and 63% were declared wrong for duty.

A distribution main survey of 132 traps classified 42% as failed. Monitoring of service life also began in 1980 and is continuing to this day. Average service life results for specific trap types are shown in Table 2-l.

To determine the energy efficiency of the various types, live steam loss tests on used traps were carried out on test rigs in the laboratories of two manufacturers. These tests were conducted at the laboratory conditions: 20°C (68’F) and still air. No measurements were made to assess heat losses from the trap bodies. Applied condensate loads were lo-20 kg/hr (22-44

lb/hr) a fairly typical loading.

Results are summarized in Table 2-2. The most interesting feature of the tables is that the thermodynamic disc trap (the general purpose and most widely used trap) is the least energy efficient and, compared with the inverted bucket trap, has a poor service life.

On applications where only modest heat input is required, substituting the thermostatic types for the disc trap would increase energy savings without reducing service life.

The tests also revealed that the mechanical types of trap, i.e.

inverted bucket and float traps, kept the steam space clear of condensate under both light and heavy load conditions, whereas the thermostatic types tended to back up condensate as load increased. Furthermore the bimetallic traps tended to be erratic in operation.

The new guide includes a trap selection chart.

(2)

TODAY’S

RJXOMMENDATIONS Inverted Bucket (IB)T.rsps Select as East choice for all process duties and steam mains drainage i.e. where the steam space must be kept clear of condensate.

Float and thermostatic traps Use on process applications especially on temperature controlled duties below 3.5 bar(g) (50 psig) or if an LB installation would lead to problems with excessive air loads.

Balanced pressure traps Select for non-critical tracing systems and heating systems.

Bimetdlic thermostatic traps Select for low temperature or frost protection on traced pipelines or heating systems,

The recommended model is adjustable to allow maximum use of sensible heat in the condensate or to prevent overheating of the product. Its body is all SS.

Thermodynamic disc traps Limit use to steam mains drainage and tracing systems up to 17 bar(g) (250 psig) as an alternative to inverted bucket traps and for replacement purposes on higher pressures if previous experience has shown that they have operated

satisfactorily. Because oftheir poor energy efficiency and relatively poor service life they are not recommended {and, at Huddersfield or Grangemouth Works not allowed).

Let? to Right - Aqustable Bimetallic Trap, Inverted Bucket Trap, Balanced Pressure Thermostatic Trap

Trap Type Thermodynamic

disc 10 - 12 months 12 months

Float and thermostatic

Inverted bucket

- 18 months

l 1 - 6 months 5 - 7 years

1

*Model dependent

L P 38 Psi (9)

2 bar (9) 5 - 7 years

* 9 months - 4 years 12-15years

5 - 7 years 7-lOyears

bp Type

hermodynamic disc

I I

1.09 (2.4) 0.84 (1.9) Inverted bucket

(average of 2 suppliers traps) Balanced pressure thermostatic

0.44 (0.97) 0.42 (0.93) Not tested 0.10 (0.22) Balanced thermostatic

Subcooled bimetallic thermostatic

NIL NIL

NIL NIL

ICI 8194 2M

Reprinted from “The ICI Engineer” January 1993 Special Issue with permission from ICI Engineering

참조

관련 문서

In addition to his professional experience, Dan spent five years as an adjunct faculty member of both The University of Miami and Florida International University

The sender of each flow uses a token bucket filter (TBF) to constrain the flow. The size of bucket buffer is set larger than the bucket size of the same TBF. Based on

Hence, it is required to meet the performance criteria of design offshore safety critical elements subjected to a specific level of risk-based explosion load

The apparatus for testing the antimicrobial activity was composed of a Black Light Blue (BLB) lamp as UV-A light source, a Petri dish as the cover material, and a polypropylene

Therefore, the fiber ply orientation and the shape of the stem need to be determined by measuring the load accurately since the load applied to the stem differs

Building heating and cooling load breakdown is carried out for the high-rise building under different locations, which the additional energy required in cooling and heating

11 shows an example of the collapse load factor and the sensitivity index, after the disappearance of a single branch member from the original frame, divided by the

Results: Compared to normal corn, both the amylose and dietary fiber contents in waxy corn were numerically lower, but the starch gelatinization degree was