Chapter 2 Installation and Wiring|VFD-B Series

2.4 Wiring

2.4.1 Basic Wiring

„ Make sure that power is only applied to the R/L1, S/L2, T/L3 terminals. Failure to comply may result in damage to the equipment. The voltage and current should lie within the range as indicated on the nameplate.

„ Check the following items after completing the wiring:

1. Are all connections correct?

2. No loose wires?

3. No short-circuits between terminals or to ground?

A charge may still remain in the DC bus capacitors with hazardous voltages even if the power has been turned off. To prevent personal injury, please ensure that the power is turned off and wait ten minutes for the capacitors to discharge to safe voltage levels before opening the AC motor drive.

DANGER!

1. All the units must be grounded directly to a common ground terminal to prevent electric shock, fire and interference.

2. Only qualified personnel familiar with AC motor drives are allowed to perform installation, wiring and commissioning.

3. Make sure that the power is off before doing any wiring to prevent electric shocks.

Basic Wiring Diagrams

Users must connect wires according to the circuit diagrams on the following pages. Do not plug a modem or telephone line to the RS-485 communication port or permanent damage may result. The pins 1 & 2 are the power supply for the optional copy keypad PU06 only and should not be used for RS-485 communication.

Chapter 2 Installation and Wiring|VFD-B Series

2-14 Revision July 2008, BE16, SW V4.08 & V5.00

AVI

ACI AUI ACM

+2/B1 B2

4~20mA -10~+10V

+10V

5K 3

2 1 Figure 1 for models of VFD-B Series

VFD007B21A/23A/43A/53A, VFD015B21A/21B/23A/23B/43A/53A, VFD022B23B/43B/53A

Jumper

Br ak e res istor (optional)

Power supply +10V 20mA Master Fr equency 0 to 10V 47K

Analog S ignal Common

DC choke (optional)

E

Main c ircui t (power) terminals Contr ol ci rcuit ter minals Shielded l eads & Cable FWD

REV JOG EF MI1 MI2 MI3 MI4

MI6 TRG MI5

DCM +24V

Sw1 Sink Source F act ory set ting :

SINK Mod e F WD/ST OP

REV/STO P JO G

E.F.

Multi-s tep 1 Multi-s tep 2 Multi-s tep 3 Multi-s tep 4 RESET Acc el/Decel prohibit

Counter Digital Signal Comm on Fac tor y

setting

* Don't apply the mains v oltage directly

to abov e terminals. E

Please refer to F ig ure 4 fo r w iring of SINK m od e and SOURCE m od e.

R(L1) S(L2) T(L3) Fus e/NF B(None F us e Br eak er)

SA

OF F ON

MC MC

RB RC

+1

Recommended Circuit when power s upply is turned O FF by a fault output.

R(L1) S(L2) T(L3)

E

Analog Multi- function Output Ter minal

factory setti ng: Analog freq.

/ c ur rent meter 0~1 0VDC/2 mA U(T1)

V(T2) W(T3)

3~ IM

MO1

MO2

MO3

AFM

ACM RA RB RC

MCM

RS-485 Motor

factory setti ng:

indicates dur ing operation 48V50mA

factory setti ng:

F req. Setting Indi cation factory setti ng:

Low-voltage Indication Multi-function Photocoulper O utput

Analog S ignal common

Seri al interface 1: EV 2: G ND

5:Reserv ed 6: Reserv ed

3: SG- 4: SG +

DFM

DCM

Digital F requency Output Ter minal

factory setti ng: 1:1 Duty =50%

Digital Signal Comm on 48V50mA

48V50mA E

E

Refer to Control Ter minal Ex pl anation

* For the single phas e driv es, the A C input line can be connected to any two of the thr ee input terminals R,S,T

* T hree phase input power may apply to single phase drives .

T he contact will be ON when the fault occur s to turn off the power and protect the power sys tem.

Chapter 2 Installation and Wiring|VFD-B Series

Revision July 2008, BE16, SW V4.08 & V5.00 2-15

Figure 2 for models of VFD-B Series

VFD022B21A, VFD037B23A/43A/53A, VFD055B23A/43A/53A, VFD075B23A/43A/53A, VFD110B23A/43A/53A

Br ak e r es istor (optional ) Refer to Appendi x B for the use of special brake resi stor

+1 +2/B1 B2 Jumper

* For the single phas e driv es, the AC input line can be connected to any two of the three input termi nal s R,S,T

* T hree phase input power may apply to single phas e driv es.

-( minus sig n) B R

DC chock (optional)

AVI

ACI AUI ACM 4~20mA

-10~+10V +10V

5K 3

2 1

Power supply +10V 20m A

Master Fr equency 0 to 10V 47K

Analog S ignal Common E FWD REV JOG EF MI1 MI2 MI3 MI4

MI6 TRG MI5

DCM +24V

Sw1 Sink Source Fact ory Setting:

SINK Mo de F WD/STOP

REV/STO P JO G

E.F.

Multi-s tep 1 Multi-s tep 2 Multi-s tep 3 Multi-s tep 4 RESET Acc el/Decel prohibit

Counter Digital Si gnal Common F ac tor y

setting

* Don't apply the mains voltage direc tly

to abov e terminals. E

Please refer to Fig ure 4 fo r w irin g of S INK mod e and SOURCE mod e.

R(L1) S(L2) T(L3) F us e/NFB(None Fuse Br eaker)

SA

OF F ON

MC

MC RB RC R(L1)

S(L2) T(L3)

E

Analog Multi- func tion Output Ter minal

F ac tor y default: A nal og freq.

/ c ur rent meter 0~1 0VDC/2 mA

MO3 U(T1) V(T2) W(T3)

3~ IM

MO1

MO2

AFM

ACM RA RB RC

MCM

RS-485 Motor

F ac tor y setting:

indicates during operation 48V50mA

Fac tor y setting:

Freq. Setting Indication

Fac tor y setting:

Low-voltage Indication

Multi-function Photocoulper Output

Analog S ignal common

Seri al interface 1: EV 2: G ND

5:Reserv ed 6: Reserv ed

3: SG- 4: SG + DFM

DCM

Digital Frequency Output Ter minal

Fac tor y setting: 1:1 Duty =50%

Digital Si gnal Common 48V50mA

48V50mA E

E

Please refer to Contr ol Ter minal Ex pl anation.

6 1

Main c irc ui t (power) terminals Contr ol c ircuit ter minals Shielded l eads & Cable Recommended Circ ui t when

power s upply is turned O FF by a fault output.

T he contact will be O N when the fault occur s to turn off the power and protect the power sys tem.

Chapter 2 Installation and Wiring|VFD-B Series

2-16 Revision July 2008, BE16, SW V4.08 & V5.00

Figure 3 for models of VFD-B Series

VFD150B23A/43A/53A, VFD220B23A/43A/53A, VFD300B23A/43A/53A, VFD370B23A/43A/53A, VFD450B43A/53A, VFD550B43C/53A, VFD750B43C/53AVFD185B23A/43A/53A,

Br ak e r es istor/unit(optional ) Refer to Appendi x B for the use of special brake resi stor/uni t

+1 +2 Jumper

VF DB

-( min us sig n) DC chock

(optional)

Main c irc ui t (power) terminals Contr ol c ircuit ter minals Shielded l eads & Cable Analog Multi- func tion Output Ter minal

factory setti ng: Analog fr eq.

/ c ur rent meter 0~1 0VDC/2 mA

MO3 U(T1) V(T2) W(T3)

IM 3~

MO1

MO2

AFM

ACM RA RB RC

MCM

RS-485 Motor

F ac tor y setting:

indicates dur ing operation 48V50mA

F ac tor y setting:

F req. Setting Indication

F ac tor y setting:

Low-voltage Indication

Multi-function Photocoulper Output

Analog S ignal common

Seri al interface 1: EV 2: G ND

5:Reserv ed 6: Reserv ed

3: SG- 4: SG + DFM

DCM

Digital F requency Output Ter minal

F ac tor y setting: 1:1 Duty =50%

Digital Si gnal Common 48V50mA

48V50mA E

E

Please refer to Contr ol Ter minal Ex pl anation

6 1

AVI

ACI AUI ACM 4~20mA

-10~+10V +10V

5K 3

2 1

Power supply +10V 20m A

Master Fr equency 0 to 10V 47K

Analog S ignal Common E FWD REV JOG EF MI1 MI2 MI3 MI4

MI6 TRG MI5

DCM +24V

Sw1 Sink Source F act ory set tin g:

SINK Mo de F WD/ST OP

REV/STO P JO G

E.F.

Multi-s tep 1 Multi-s tep 2 Multi-s tep 3 Multi-s tep 4 RESET Acc el/Decel prohibit

Counter Digital Si gnal Common F ac tor y

setting

* Don't apply the mains voltage directly

to abov e terminals. E

Please refer to F ig u re 4 fo r w irin g of SINK m od e an d SOURCE m od e.

R(L1) S(L2) T(L3) F us e/NF B(None F use Br eaker)

SA

OF F ON

MC

MC RB RC R(L1) +1

S(L2) T(L3)

E

* For the single phas e driv es, the AC input line can be connected to any two of the three input termi nal s R,S,T

* T hree phase input power may apply to single phas e driv es.

Recommended Circui t when power s upply is turned O FF by a fault output.

T he contact will be O N when the fault occur s to turn off the power and protect the power sys tem.

Chapter 2 Installation and Wiring|VFD-B Series

Revision July 2008, BE16, SW V4.08 & V5.00 2-17

Figure 4 Wiring for SINK mode and SOURCE mode

Factory setting SINK Mode

*Don't apply the mains voltage directly to above terminals.

FWD/STOP REV/STOP

Multi-step1 Multi-step2 Multi-step3 Multi-step4

Digital Signal Common

+24V

MI1 MI2 MI3 MI4 MI5 MI6

DCM E Sink

Source SW1

FWD REV JOG EF

TRG JOG

E.F.

RESET

Accel./Decel. prohibit Counter

Sw1 Sink

Source

Factory setting SOURCE Mode

*Don't apply the mains voltage directly to above terminals.

FWD/STOP REV/STOP

Multi-step1 Multi-step2 Multi-step3 Multi-step4

Digital Signal Common

+24V

MI1 MI2 MI3 MI4 MI5 MI6

DCM E

FWD REV JOG EF

TRG JOG

E.F.

RESET

Accel./Decel. prohibit Counter

Chapter 2 Installation and Wiring|VFD-B Series

2-18 Revision July 2008, BE16, SW V4.08 & V5.00

문서에서 Chapter 1 Introduction ... 1-1 (페이지 30-35)